REP -15 relay intermediate – Energy Industrial Company

The REP-15 relay, the REP-15 relay intermediate are designed for use in the circuits of electric drives in all sectors of the national economy, except for moving devices and conditions with aggressive environments. Relay contacts are designed for switching alternating current circuits with a rated voltage up to 660 in frequencies of 50 (60) Hz and DC with a rated voltage up to 220 V.

Without Kevordo

Top

Energy -industrial company

Main menu

Products

Home Relay, Relay equipment REP REP-15 Relay Intermediate

REP-15 relay is intermediate
Control relay

REP-15 relay is intermediate Designed for use in circuits of electric drives in all sectors of the national economy, except for moving devices and conditions with aggressive environments.

Relay contacts are designed for switching alternating current circuits with a rated voltage up to 660 in frequencies of 50 (60) Hz and DC with a rated voltage up to 220 V.

The REP-15 relay is allowed as a magnetic starter for controlling low-power AC engines.

Relays, component by OPN overstrain limiters, are suitable for working in control systems using microprocessor equipment.

Stop restraints limit switching overvoltages on the clamps of the relay coil to size:

  • on a direct current coil – no more than 2 -fold nominal;
  • On an alternating current coil-no more than 2-fold amplitude value for voltages of 110, 220, 380 V and 4-fold amplitude value for voltages of 24 and 48 V (taking into account the permissible increase in voltage to 110% of the nominal value).

Joining external conductors: front
Nominal contact voltage, c:

  • Variable current – 12-660
  • DC – 12-220

Nominal current of contacts, A: 6
The smallest nominal working current of contacts, a:

  • at a voltage of 12V – 0.025
  • at a voltage of 24V – 0.01

Permissible end -toe of contacts for 1 s, a: 120
Permissible limits of changing the voltage of the control circuit, from the nominal: 0.85? 1.1
Switching wear resistance, no less:
-for an alternating current relay with a power of 456, voltage 380 V in the category of AS-11 or 44 V voltage 220 V in the category of DS-11

  • wear resistance class – A: 2
  • Class of reduced wear resistance – B: 1

-for a direct current relay with a 190-powered power voltage 380 V in the category of AS-11 or 29 W, voltage 220 V in the category of DS-11

  • wear resistance class – A: 4
  • Class of reduced wear resistance – B: 2

Mechanical wear resistance, no less:

  • Variable current – 20,000,000
  • DC – 10,000,000

Power consumption in the heated state of the relay REP15 at ambient temperatures (20 ± 5) ° C and nominal voltage, no more: no more:

  • alternating current, VA – 7 ± 1
  • DC, W – 6

The operation time at ambient temperatures (20 ± 5) ° C and rated voltage, C, no more: no more:

  • A variable current – 0.03
  • DC – 0.05

Return time at ambient temperature (20 ± 5) ° C and rated voltage, C, no more than: 0.03
Opening hours:

  • Long
  • intermittently
  • short -term
  • repeated-short (with an inclusion frequency up to 1200 per hour and PV 40%)

Mechanical influences for the group of operating conditions according to GOST 17516-72: M7
Ambient temperature, ° C

  • U3 – from -45 to +55
  • T3 – from +1 to +55

Relative humidity, at ambient temperatures +20 ° C, %, no more than: 90
The climatic execution of the relay according to GOST 15150-69 (the climate execution of the Uz is suitable for operation in the conditions of UHL4 according to GOST 15150-69): UZ and TK

The relay is adjusted to the operation at voltage on the clamps of the coil 0.85? 1.05 nominal.
Installation of the contact prefix on the relay of the REP 15-220 series, REP 15-310, rap 15-400 is unacceptable.
On a separate order, the coils and restriction limiters are delivered for an additional fee.